SDN-P Series Power Supply (Single
and Three Phase Units, 60-960 Watts)
The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications. Power factor correction to meet European directives, hazardous location approvals and optional
redundant accessories allow the SDN series to be used in a wide variety of applications. Wide operation temperature range, high tolerance to shock and vibration and reliable design make the SDN series the preferred choice of
users everywhere.
ATEX approval on 2.5 through 10A, 24 Vdc Single Phase Models
Improved metal mounting clip
DC OK Signal
Adjustable Voltage
SDN10-24-100P New Compact width (3.26)
Parallel Capability standard on all units
Industrial grade design
- 10oC to 60oC operation
without derating. Indefinite short circuit, overvoltage and overtemperature
protection.
- Powers high inrush loads without shutdown
or foldback
-
Rugged metal case and DIN connector
SDN2.5-24-100P and SDN4-24-100LP meet NEC Class 2
Narrow width on rail for space critical applications
EN60950; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, IEC60079-15 (Class 1, Zone 2, Hazardous Location, Groups A, B, C, D w/ T3A
temp class up to 60°C Ambient.) SEMI F47 Sag Immunity. SDN 2.5 & SDN 4 - UL60950 testing to include approval as Class 2 power supply in accordance with UL1310.
Temperature
Storage: -25°C...+85°C Operation. -10°-60°C full power with operation to 70°C possible with a linear derating to half power from 60°C to 70°C (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
Humidity
The relative humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3.
MTBF:
> 820,000 hours
> 640,000 hours
> 600,000 hours
> 510,000 hours
-Standard
Bellcore Issue 6 Method 1 Case 3 @ 40°C
MIL STD 217F @ 30°C
Warranty
5 years
General Protections/
Safety
Protected against continuous short-circuit, overload, open-circuit.
Protection Class 1 (IEC536),
degree of protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950)
Status
Indicators
Green
LED and DC OK signal (N.O. Contacted rated 200 mA @ 60 Vdc)
Installation
Fusing
-Input
Internally
fused. External 10 A slow acting fusing for the input is recommended
to protect wiring
-Output
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if
2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Mounting
Simple
snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional
screw mounting set SDN-PMBRK2 required).
Connections
Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: Two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid conductors.
Case
Fully
enclosed metal housing with fine ventilation grid to keep
out small parts
-Free
Space
25
mm above/below
25 mm left/right, 10 mm in front
25
mm above/below
25 mm left/right
15 mm in front
70
mm above/below
25 mm left/right, 15 mm in front
H
x W x D
(inches/mm)
4.88
x 1.97 x 4.55
(124 x 50 x 116)
4.88
x 2.56 x 4.55
(124 x 65 x 116)
4.88
x 3.26 x 4.55
(124 x 83 x 116)
4.88
x 6.88 x 4.55
(124 x 175 x 116)
Weight
(lbs/g)
1
lb (.45 kg)
1.5 lb (.68 kg)
2.2
lbs (0.1 kg)
3
lbs ( 1.36 kg)
Notes: 1. Not UL listed for DC input.
2. Input current ratings are conservatively specified with low input, worst case efficiency and power factor.
3. Losses are heat dissipation in watts at full load, nominal input line.
4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
5. Full load, 100 Vac Input @ Tamb = +25°C
Specifications
(Single Phase), 12 and 48 Vdc Output
Description
Catalog
Number
SDN
9-12-100P
SDN
5-48-100P
SDN
16-12-100P
Input
Nominal
Voltage
115/230
Vac user select (no manual required)
-AC Range
85-132/176-264
Vac
-DC Range1
210
- 375 Vdc
-Frequency
47
- 63 Hz
Nominal Current2
2.0
A / 1.5 A
4
A / 2.3 A
3.3
A / 1.7 A
-Inrush
current max.
typ. < 20 A
typ. < 40 A
Efficiency (Losses3)
>84%
typ (17.28 W)
>88%
typ (28.8 W)
>84%
typ (30.72 W)
Power
Factor
Correction
Units
fulfill EN61000-3-2
Output
Nominal Voltage
12
V (11.8
- 15.2 Vdc Adj.)
48 Vdc (35.8 - 52 Vdc Adj.)
12 V (11.6 - 14.0 Vdc Adj.)
Tolerance
<±2%
overall (combination
line, load, time and temperature related changes)
-Line Regulation
< 0.5%
-Load Regulation
< 0.5%
-Time & Temp. Drift
< 1%
-Ripple4
< 50 mVpp
Overvoltage Protection
< 16 Vdc with auto-recovery
< 60 Vdc with auto-recovery
< 16 Vdc with auto-recovery
Nominal Current
9
A (108 W)
5
A (240 W)
16
A (192 W)
-Current Limit
110% of nominal - Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current)
Holdup
Time5
>20 ms (Full load, 100 Vac Input @ Tamb=+25°C) to 95% output Voltage
Parallel Operation
Supplies will not be damaged with parallel operation
Power Back Immunity
16 Vdc
60 Vdc
16 Vdc
General
EMI
-Emissions
EN61000-6-3, EN61204-3, EN55022 Class B, EN61000-3-2, EN61000-3-3
UL508 Listed, cULus; UL 60950-1, cURus; CE (LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC). EN61000-3-2;
UL 60079-15
(Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC w/ T3 temp. class up to 40°C Ambient.);
SEMI F47 Sag Immunity, RoHS
Temperature
Storage: -25°C...+85°C Operation. -10°-60°C full power with operation to 70°C possible with a linear derating to half power from 60°C to 70°C
(Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
Humidity
< 90% RH, noncondensing; IEC 68-2-2, 68-2-3.
MTBF:
> 500,000 hours
-Standard
Telcordia/Bellcore, Issue Case 3 @25oC
Warranty
5 years
General Protections/ Safety
Protected against continuous short -circuit, continuous overload, continuous open circuit. Protection Class 1 (IEC536),
Degree of Protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950)
Status Indicators (Visual)
Green LED on when Vout > 75% (with ± 5% tolerance) of nominal output voltage
Status Indicators (Relay)
Normally Open solid state relay - signal active when Vout >70% of nominal output voltage (rated up to 200 mA, 60 Vdc)
Installation
Fusing
-Input
Internally
fused.
-Output
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for
wire/loads if Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Mounting
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Unit should handle normal shock and vibration
of industrial use
and transportation without
falling off the rail.
Connections
Input: Screw terminals, connector size range: 16-10 AWG (1.5-6mm2) for solid conductors.
Output:Two terminals per output, connector size range: 16-10 AWG (1.5-6mm2) for solid conductors.
Case
Fully
enclosed metal housing with fine ventilation grid to keep
out small parts
-Free
Space
70
mm above/below, 25 mm left and right, 15 mm in front
H
x W x D (inches/mm)
4.88
x 2.56 x 4.55 (124 x 65 x 116)
4.88
x 3.26 x 4.55 (124 x 83 x 116)
Weight
(lbs/kg)
2.4 (1.05 kg)
3.3 (1.48)
Notes: 1. Input current ratings are specified with low input, line conditions and worst case efficiency values. Input current at nominal input settings will be typically half these values.
2. Losses are heat dissipation in watts at full load, nominal line.
3. Ripple/ noise is stated as typical values when measured with a 20 MHz bandwidth
scope and 50 Ohm resister.
4. Unit shall not shutdown or ‘hiccup’ during overload or short circuit. Maximum current value shown shall be maintained indefinitely without damage to the supply. Voltage shall drop according to amount of overload to protect supply from damage.
CB Scheme, EN60950; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, UL60079-15
Class 1, Zone 2 Hazardous Location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient.
Temperature
Storage:
-25oC...+85oC Operation. -10o-60oC
full power with operation to 70oC possible with
a linear derating to half power from 60oC to 0oC. (Convection cooling, no forced air
required). Operation up to 50% load permissible with
sideways or front side up mounting orientation.
The relative humidity is less <90% RH, noncondensing;
IEC 68-2-2, 68-2-3.
MTBF
> 1,110,000 hours
> 940,000 hours
> 550,000 hours
> 620,000 hours
> 490,000 hours
-Standard
MIL STD 217F @ 30oC
Warranty
5
years
General Protection/
Safety
Protected against continuous short-circuit,
overload, open-circuit. Protection Class 1 (IEC536), degree
of protection IP20 (IEC 529) Safe low voltage: SELV
(acc. EN60950)
Status Indicators
Green
LED on, when Vout = 18V or greater.
Installation
Fusing
-Input
Internally
fused.
-Output
Outputs
are capable of providing high currents for short periods of
time for inductive load startup or switching. Fusing may be
required for
wire/loads if 2x Nominal O/P current
rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Mounting
Simple
snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional
screw mounting set SDN-PMBRK2 required).
Connections7
Input:
IP20 related screw terminals, connector size range: 16-10
AWG (1.5-6 mm2) for solid conductors. 16-12
AWG (0.5-4 mm2) for stranded conductors. Output: two connectors per output,
connector size range: 16-10 AWG (1.5 - 6 mm2) for
solid connectors.
Case
Fully
enclosed metal housing with fine ventilation grid to keep
out small parts.
-Free
Space
25
mm above/below, 25 mm left/right
15 mm in front
70
mm above/below, 25 mm left/right
15 mm in front
H
x W x D
(inches/mm)
4.88
x 2.91 x 4.55
(124 x 73 x 116)
4.88 x 3.5 x 4.55
(124 x 89 x 116)
4.88 x 5.9 x 4.55
(124 x 150 x 116)
4.88 x 9.72 x 4.55
(125 x 247 x 116)
4.88
x 11.1 x 4.55
(125 x 282 x 116)
Weight
(lbs/kg)
1.7
(.77)
2.16 (.98)
3.97 (1.8)
4
(1.81)
6.6
lbs (2.99)
Notes: 1. For the SDN 20-24-480C, single phase input is permissible, but output is derated to 75% (15 Amps @ 24 Vdc).
2. Not UL listed for DC input.
3. Input current ratings are conservatively specified with low input, worst case efficiency and power factor.
4. Losses are heat dissipation in watts at full load, nominal input line.
5. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
6. Full load, 100 Vac Input @ Tamb = +25°C
7. For the SDN 40-24-480, output: one (+) two (-) connectors, size range 16-5 AWG (1.5016 mm2) solid conductor.
Instead of snapping a Sola SDN power supply unit on the DIN Rail, you can
also attached it using the screw mounting
set SDN-PMBRK2.
This
set consists of two metal brackets which replace the existing
two aluminum profiles.
Note:
You need one SDN-PMBRK2 per unit.
In addition, two screws are required per SDN-PMBRK2 (e.g. M5 x 12), which are not included
with the set.