The SDN-C DIN rail power supplies are the next generation of the popular SDN series. These models combine high
efficiency and compact size with new visual diagnostic LEDs to offer the most performance available from SolaHD. Essential industrial features such as Sag Immunity, Power Factor Correction, and universal voltage input have been retained in this series. Wide temperature operating range and parallel operation capability make the new SDN-C units suitable to a variety of industrial applications.
Overview
|
|
A printable version of the following sections is available by selecting the
pdf file to the left.
|
- Compact packaging to save space on the DIN rail
- New visual diagnostics LEDs for input and output status
- High MTBF means high reliability and long life
- Higher efficiency saves energy and lowers amount of heat generated in panel
- PowerBoostTM overload capability to start high
inrush loads
- Accepts Universal voltage 85-264 Vac, 50/60 Hz input
- Single phase models meet SEMI F47 Sag Immunity standard
- Power Factor Correction (meets EN61000-3-2)
- Class I, Div 2 Hazardous Locations rating
– ATEX approval (pending)
- Patented DIN rail mounting clip
- User Adjustable output voltage accessible via front face
- Parallel capability standard
- Industrial grade design
– -25oC to 60oC operation without derating
– Rugged metal case and DIN connector
- User-friendly
– LEDs for status
– Large, rugged, accessible screw terminals
– Easy on/off DIN mounting
- Fully tested and burned-in at factory
- RoHS compliant
|

EMC and
Low Volt.
Directive |

UL 508 Listed
IND CONT. EQ.
E61379 |

UL 60950-1
E137632
CAN/CSA-C22.2
No. 60950-1 |
|
- Industrial Machine
Control
|
|
|
|
|
|
|
|
|
|
- Semiconductor Fabrication Equipment
|
- Chassis
Mount Bracket (SDN-PMBRK2)
| Specifications |
 |
|
Description
|
Catalog
Number |
| SDN
5-24-100C |
SDN 10-24-100C |
SDN
20-24-100C |
|
Input
|
| Nominal Voltage |
115/230 Vac |
|
-AC Range |
85 - 264 Vac
|
|
-DC Range1 |
90 - 375 Vdc |
|
-Frequency |
43-67 Hz |
| Nominal Current2 |
1.65 - 0.55 A |
3.2 - 1.0 A |
6 A / 3 A |
|
-Inrush current max. |
Typ. < 15 A |
Typ.< 30 A |
< 40 A |
| Efficiency (Losses3) |
> 90% typ. (12 W) |
> 90% typ. (24 W) |
> 92% (38 W) |
| Power
Factor
Correction |
Active Power Factor Correction to better than 0.92
|
|
Output
|
| Nominal Voltage |
24 V (23.5-28.5 Vdc Adj.) |
| -Tolerance |
< ±2 % overall (combination line, load, time and temperature related changes) |
| Initial Voltage Setting |
|
| -Ripple4 |
< 50 mVpp
|
< 100 mVpp |
| PARD |
PARD (Periodic and Random Deviation) = 100 mV peak-peak max
|
| Overvoltage Protection |
> 30.5 but < 33 Vdc, auto recovery
|
| Power Back Immunity |
|
| Nominal Current |
5 A (120 W) |
10 A (240 W) |
20
A (480 W) |
| -Peak Current5 |
1.5 × Nominal Current for 2 seconds minimum while holding voltage > 20 Vdc |
| -Short Curcuit Current |
1.5 x Nominal Current at near zero volts at short circuit condition |
| -Current Limit |
PowerBoost™ |
| Parallel Operation |
Switch selectable single unit or parallel unit operation. Units will not be damaged by parallel operation (regardless of switch position setting). |
| Holdup Time |
>20 ms (Full load, 100 Vac Input @ Tamb=+25°C) to 95% output voltage |
| Voltage Fall Time |
<150 mS from 95% to 10% rated voltage @ full load (Tamb=+25°C)
|
| Line and Load Regulation |
|
|
General
|
EMI
-Emissions |
EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2 |
| -Immunity |
EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input
and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, IEC 61000-4-34 voltage dip immunity standard |
| Approvals |
UL508 Listed, cULus; UL 60950-1, cURus; IEC60950-1; Class I, Div. 2, Hazadous location approval; CE (LVD 73/23 & 2004/108/EC), (EMC 89/336 & 93/68/EEC); EN61000-3-2
|
| Temperature7 |
Storage: -40 to + 85oC, Operation -25 to +60oC full power, with linear derating to half power from 60 to 70oC (Convection cooling, no forced air required). Operation up to 50% load permissable with sideways or front side up mounting orientation. |
| MTBF6 |
> 550,000 hrs |
> 450,000 hrs |
| Warranty |
5 Years |
General Protections/
Safety |
Protected against continuous short -circuit, continuous overload, continuous open circuit.
Protection Class 1 (IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1) |
| Status
Indicators |
Visual: 3 status LEDs (Input, Output, Alarm)
Relay: N.O. contact rated 200ma/50 Vdc |
|
Installation
|
| Fusing |
| -Input |
Internally fused |
| -Output |
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. |
| Mounting |
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. |
| Connections |
Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6 mm2
) for solid conductors. |
| Case |
Fully enclosed metal housing with fine ventilation grid to keep out small parts. |
| -Free
Space |
15 mm in front, 25 ~ 40 mm above and below, 10 mm left and right. |
| H
x W x D (inches/mm) |
4.88 × 1.97 × 4.55
(124 × 50 × 116) |
4.88 × 2.36 × 4.55
(124 × 60 × 116) |
4.88 × 3.42 × 4.98
(124 × 87 × 126.6) |
| Weight
(lbs/kg) |
1.65 (0.75) |
1.98 (0.9) |
2.6 (1.2) |
Notes:
1. Not UL listed for DC input.
2. Input current ratings are conservatively specified with low input, worst case efficiency and power factor.
3. Losses are heat dissipation in watts at full load, nominal input line.
4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
5. Peak current is calculated at 24 Volt levels.
6. Demonstrated through extended life test.
7. Contact tech support for operation at -25oC.
|
|
Normal |
AC Power Loss |
AC Input Low |
No DC |
High Load |
Overload |
Hot |
Too Hot |
Input |
Green |
- |
Yellow |
Green |
Green |
Green |
Green |
Green |
Output |
Green |
- |
Green |
- |
Yellow |
Yellow |
Green |
- |
Alarm |
- |
- |
- |
Red |
Yellow |
Red |
Yellow |
Yellow |
|
|
Catalog Number |
Dimensions |
H |
W |
D |
SDN
5-24-100C
|
4.88
(124) |
1.97 (50) |
4.55
(116) |
SDN 10-24-100C
|
4.88 (124) |
2.36 (60) |
4.55 (116) |
SDN 20-24-100C |
4.88 (124) |
3.42 (87) |
4.98 (126.6) |
DIN RAIL Mounting
Snap on the DIN Rail:
1. Tilt unit slightly backwards.
2. Put it onto the DIN Rail.
3. Push downwards until stopped.
4. Push at the lower front edge to lock.
5. Shake the unit slightly to ensure
that the retainer has locked.
|
|
|
Alternative Panel Mount: Using the optional SDN-PMBRK2
accessory, the unit can be screw mounted to a panel.
|
| Detachment
from DIN Rail: |
|
|
|
|
Press button downwards (to unlock)
and remove the
unit from the DIN Rail. |
Instead of snapping a Sola SDN power supply unit on the DIN Rail, you can
also attached it using the screw mounting
set SDN-PMBRK2.
This
set consists of two metal brackets which replace the existing