SOLATRON™ Plus Series - Three Phase Power Conditioner

These three phase power conditioner units protect equipment from voltage sags and spikes, switching transients, lightning, and induced surges by a carefully designed surge suppression circuit linked to a shielded isolation transformer and input and output filters.

These power conditioner units hold output voltage regulation to a maximum of ±5%, even with an input voltage window of +15% to -25%. Response time to any line variation is 1.5 cycles regardless of power factor. The power conditioner units operate with 150 dB Common Mode noise attenuation and 65 dB Normal Mode noise attenuation at 100 kHz.

TPC Series power conditioner
On this page: Features, Applications, Related Products, Specifications, Selection Table

cClick here to view certificate.US

A printable version of the following sections is available by selecting the pdf file to the left.

Features Top

  • Rugged, industrial design
  • High overload capability
  • High MTBF - No fans used
  • No power factor restriction on loads
  • Tight regulation of ±3% for protection against sag (-25%) and swell (+15%) conditions
  • Fail-safe, no-break, auto-bypass
  • Status indicating lights
  • Shielded, copper wound isolation transformer
  • Surge suppression to ANSI/IEEE and IEC Standards
  • High efficiency (96%) microprocessor controlled tap switcher
  • Automatic under voltage protection
  • UL1012, UL1449-2, cULus Listed
Applications Top

  • Automatic Packaging Machinery
  • Large Machine Tool Equipment
  • UPS Bypass Circuits
  • Retail Store
  • Process Equipment

Related Products Top

  • STV100K Surge Suppressors
  • General Purpose Transformers

Specifications Top

Mechanical

 Indicators   Indicating Lamps: 2 amber (overtemperature and bypass mode)
 1 green (regulated output present)
 Connections  Field wired, terminal blocks
 Size and Weight  See Selection Table
 Safety Agency Approvals  UL1012 and UL1449-2
 cUL (Canadian Standard C22.2 No 125) Complies with Part 15 Subpart J  of  FCC rules for a Class A computing device

Environmental

 Audible Noise  Less than 50 dBA at 3 feet
 Ambient Temperature  0° to 40°C Operating, 0° to 80°C Storage
 Operating Altitude  10,000 feet without derating
 Operating Humidity  95% relative (non-condensing)

Electrical

 Power Ratings  20, 30, 50, 75 KVA, Three Phase
 Nominal Voltages  See Selection Table
 Input Voltage Range  -25% to +15% of nominal rated voltage.
 Output Voltage Range  Regulated to ± 5% of nominal voltage with
 an input voltage range of –25% to +15%.
 Response Time   Responds to any line variation in <1.5 cycles typical.
 Technology   Enhance Voltage Regulation (EVR), Microprocessor controlled electronic  tap switching. 6 taps switched at zero current crossing with no output
 interruption.
 Operating Frequency  57-63 Hz
 Load Power Factor  No Restriction
 Insulation Resistance  100 megohms from winding to core measured at 500 VDC
 Efficiency  96% typical
 Overload Capability  1000% of rated load for 1 second,
 200% of rated load for 1 minute.
 EMI  Less than 0.2 gauss at a distance of 3 ft.

Protection

 Under Voltage  Output voltage will switch to bypass mode when input is less than 50% of  nominal. Regulated output voltage will be reestablished once input voltage  is with specifications.
 Short Circuit Protection   Input circuit breaker
 Over Temperature Protection  Amber lamp indication of over temperature at approximately 
 180°C. Unit switches to by-pass mode until internal temperature is reduced  to specified values.

Noise Suppression Performance

 Common Mode Noise Attenuation  150 dB at 100 kHz
 Normal Mode Noise Attenuation  65 dB at 100 kHz
 Surge Suppression  Tested to ANSI/IEEE standard C62.41 A&B
 (IEEE 587 Cat A and B), 1000-4, 1000-5

 

Selection Table Top

 

Output
KVA
Catalog
Number
VAC
Input
Dimensions
H x W x D (in/cm)
Ship Weight
(lbs/kg)
208 VAC Input, 208Y/120 VAC Output, 60 Hz
20 63TAA320 208 42 x 28 x 26 (1016 x 712 x 661) 600/273
30 63TAA330 208 42 x 28 x 26 (1016 x 712 x 661) 750/341
50 63TAA350 208 42 x 28 x 26 (1016 x 712 x 661) 950/432
75 63TAA375 208 42 x 28 x 26 (1016 x 712 x 661) 1200/545
480 VAC Input, 208Y/120 VAC Output, 60 Hz
20 63TCA320 480 42 x 28 x 26 (1016 x 712 x 661) 600/273
30 63TCA330 480 42 x 28 x 26 (1016 x 712 x 661) 750/341
50 63TCA350 480 42 x 28 x 26 (1016 x 712 x 661) 950/432
75 63TCA375 480 42 x 28 x 26 (1016 x 712 x 661) 1200/545
480 VAC Input, 480Y/277 VAC Output, 60 Hz
20 63TCC320 480 42 x 28 x 26 (1016 x 712 x 661) 600/273
30 63TCC330 480 42 x 28 x 26 (1016 x 712 x 661) 750/341
50 63TCC350 480 42 x 28 x 26 (1016 x 712 x 661) 950/432
75 63TCC375 480 42 x 28 x 26 (1016 x 712 x 661) 1200/545
600 VAC Input, 208Y/120 VAC Output, 60 Hz
20 63TDA320 600 42 x 28 x 26 (1016 x 712 x 661) 600/273
30 63TDA330 600 42 x 28 x 26 (1016 x 712 x 661) 750/341
50 63TDA350 600 42 x 28 x 26 (1016 x 712 x 661) 950/432
75 63TDA375 600 42 x 28 x 26 (1016 x 712 x 661) 1200/545