Sola/Hevi-Duty
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Product Specials
Password Protected Area for Reps/Distributors

PDF Links
Specifications
Printable version of S5K Modular UPS information Guide Specs
Printable version of S5K Modular UPS information Site Planning Databook


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.

Products
Home > Products > Uninterruptible Power Systems > S5K Series

S5K Modular Series Uninterruptible Power Systems (UPS)

This easily upgradeable and flexible UPS provides the protection you want, when you need it.

The 5K Modular is scalable from 4 to 20 KVA, offering many flexible options by adding a few standard modules. Designed to be fully configured, tested and shipped in the configuration you need, the 5K Modular also has the ability to be easily upgraded in the field to either higher VA ratings (up to 20 KVA maximum), longer runtimes or to add N+x parallel redundancy. Configurations can be cost-effectively upgraded keeping your 5K Modular current without a large reinvestment in a new system.

The optional N+x redundancy provides a fault-tolerant group of power modules and controls. The modular design is easy to upgrade so the UPS can grow with the needs of the system that is being protected.

Each of the modular components, including 4 KVA power modules, battery modules and system control modules, can be hot-swapped making it easy to increase power, extend your backup runtime or add redundancy while still providing power protection to the load.


This fault-tolerant system uses intelligent power and battery modules which take themselves off-line if there is a problem — without interrupting power to the load. Self-diagnostic capabilities simplify maintenance and troubleshooting. Each unit incorporates an internal automatic bypass.

Applications Top
  • Network servers
  • Enterprise telecommunications systems
  • Clusters of PCs or workstations and peripherals
  • LAN gateways, bridges and routers
  • Mini-computers, superservers and server clusters
  • RAID arrays and other large-scale data handling system
Features   Top
  • Scalable for capacity, redundancy, or battery run time offering unbelievable flexibility
  • Built-in intelligence is provided for each individual module using microprocessor controls, increasing functionality, communications and reliability
  • N+x parallel redundancy is easily achieved by adding extra control, power and battery modules
  • Any failed module will automatically take itself off-line while the other modules continue to
    support the connected equipment
  • Multiple and simultaneous communication ports
  • Variable input voltage range minimizes battery operation to increase battery life
  • An automatic internal bypass for maximum availability of output power
  • Continuous sinewave output
  • Power factor corrected input reduces reflected distortion and optimizes utility power
  • Two-year limited warranty (Includes factory start up)
Chassis Options Top

The S5K Modular has two chassis available to build on. 

  • The "A" chassis can accommodate up to 8 modules
  • The "B" chassis can accommodate up to 12 modules and supplies 16 KVA of power with N+1 redundancy
  • The "C" chassis can accommodate up to 12 modules and supplies a full 20 KVA of power with N+1 redundancy

System control modules are not included in module count. All chassis can accommodate up to two system control modules. Select the proper chassis based on your futures need for expansion or redundancy. In most standard (non-redundant) applications, the “A” chassis is the most popular.  

Selection Steps Top
  1. Determine the maximum KVA you will need for future expansion.
  2. Determine the KVA and run time value for your immediate need.
  3. Determine if you need redundancy. If the exact run time is the critical need, use the fully redundant option (see Selection Charts).
  4. Select the unit that meets both your immediate requirements, and is expandable to your future needs in the "Maximum Upgrade" column in the selection table. The Maximum Upgrade column shows the highest KVA expansion that particular configuration is capable of without removing any of the battery modules from the original configuration.
Specifications Top

Description Value

 Capacity (VA/Watts)

4 KVA / 2.8 kW to 20 KVA / 
14 kW in 4 KVA / 2.8 kW increments
Dimensions - inches
 Unit (H x W x D) 8 module capacity ""A"" Chassis 41"" x 20"" x 28""
12 module capacity ""B"" Chassis 54"" x 20"" x 28""
 Shipping (H x W x D) 56" X 32" X 42"
Input AC Parameters
 Voltage Range (typical) 170-276 VAC Low line limit variable with load
170 VAC from 80 to 100% load
144 VAC from 20 to 90% load
127 VAC from 20 to 70% load
100 VAC at less than 30% load
 Voltage Configuration
 and Connection
Single phase, 2-wire plus ground (L1-L2-G)
 Frequency 60 Hz nominal
40 - 70 Hz range without operating from battery
 Input Connector  Hardwired only
 Power Factor .98 typical
Output AC Parameters
 Voltage 240, 208, 240/120 (120-0-120 ) or 208/120(120-0-88)
 Receptacles Optional with use of external Maintenance Bypass
 Voltage Regulation  ± 3 %
 Voltage Distortion  Maximum 3% THD for linear loads, 
maximum 7% THD for full non-linear loads.
 Transient Response  < 7% for 100% step load; recovery within 96 ms.
 Frequency 60 Hz
 Frequency Slew Rate  Selectable up to 5 Hz/sec 
 Frequency Sync Selectable up to ±5 Hz 
 Range Overload 100 to 110% for 10 minutes minimum
111 to150% 10 seconds
151 to 200% for 2 Cycles
Battery Parameters
 Battery Type Sealed, lead acid
 Recharge Rate  3 to 5 hours to 90% capacity
 Battery Runtime See Selection Tables for specific configurations
Autonomy time is 6 minutes with an equal number of battery & 
power modules in a non-redundant configuration at full load
 Battery Voltage 120 VDC Nominal
 Maximum charge
current (full load)
3A
Environmental
 Operating
 Temperature     
+32oF to +104oF (0oC to +40oC)
 Storage Temperature +5oF to +122oF (-15oC to +50oC) 
 Relative Humidity 0% to 95%, non-condensing
 Operating Elevation Up to 10,000 ft. (3000m) at 104oC (40oC) without derating
 Storage Elevation  15.000m (50,000 ft.) maximum 
 Heat Dissipation  1062 BTU / hour per fully loaded power module (4 KVA / 2.8 kW)

 Audible Noise

< 62 dBA @ 1 meter 
Agency
 Safety UL 1778 listed; c-UL
 Compliant Immunity
 Standards 
ANSI C62.41, Class A & B
 Routine Maintenance

Keep the UPS clean and cool to enhance system reliability. Occasionally clean or replace the fan intake filters to ensure proper airflow. Do not use liquid or aerosol cleaning fluids. Periodically review the UPS alarm logs.

 

Recommended Part Numbers Top

See Selection Charts for other options.

KVA/kW P/N#
(Standard)
P/N#
(Redundant)
Runtime
(Min@FL/HL)
4 / 2.8 S5KA4N1A6 S5KA4R1A6  7 / 18
8 / 5.6 S5KA8N2A6  S5KA8R2A6   7 / 18
12 / 8.4 S5KA12N3A6  S5KA12R3A6   7 / 18
16 / 11.2 S5KA16N4A6 S5KB16R4A6  7 / 18
20 / 14 S5KC20N5A6 S5KC20R5A6  7 / 18

 

Mechanical Diagram Top



 

Part Number Configuration  Top

The Sola 5K modular is available in many combinations. Use the part number template below to identify the description of any given part number.

Series Designation Chassis Size KVA 
Rating
Unit 
Type
Number of Battery Modules Output
Voltage
Frequency
A = 8 Module Capacity 4, 8, 12, 16 or 20 KVA

00 = External Battery

n
N = Standard
(Not Redundant)
* Must be at least one per 4 KVA of capacity

n

A = 208/120 
1 x 1

n

6 = 60 Hz
B = 12 Module, 16 KVA Capacity R = Redundant
Power & Control
5 = 50 Hz
C = 12 Module, 20 KVA Capacity X = Redundant Power, Battery 
& Control
X
D = External Battery Cabinet B = Battery 
Cabinet

Example: 4 KVA Load, Future Expandable to 16 KVA with 7 minutes of runtime. 
What is the part number?
S5K A 4 N 1 A 6
nResulting Catalog Number is "S5KA4N1A6".n