Sola/Hevi-Duty
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps/Distributors
Product Specials

PDF Links
Catalog Pages
Guide
Specifications


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.

 

Products
Home > Products > UPS > S3K2U Series > Specifications


Sola S3K2U Specifications

A printable version of the following section is available by selecting the pdf file to the left.

3K2U Rackmount 120 VAC Top

Catalog Number

S3K2U1000
S3K2U1440
S3K2U2200
 Power Rating
 
(VA/Watts)
1000/750
1440/1080
2200/1650
Dimensions inches (mm)
 Unit 
 
(H x W x D)
3.43" x 17" x 22"
(87 mm x 430 mm x 557 mm)
3.43" x 17" x 24.1"
(87 mm x 430 mm x 612 mm)
 Shipping 
 
(H x W x D)
11.8" x 23.5" x 27.8"
(300 mm x 598 mm x 706 mm)
13.1" x 23.5" x 34"
(333 mm x 598 mm x 864 mm)
 Approx. Shipping
 Weight -  
lbs (kg)
81 (37)
86 (39)
96 (44)
Input AC Parameters
 Voltage Range
78-150 VAC
 Surge Protection
570J
 Voltage Range Without
 Battery
78-150 VAC
 Frequency
48-65 Hz ( ± 0.1 Hz)
 Input Power Cord
 10 ft. (3m) attached NEMA5-15D
10ft. (3m) attached NEMA L5-30P
Output AC Parameters
 Voltage
110/120/127 VAC ± 10% (configurable)
 Receptacles
(8) NEMA 5-15R
(8) NEMA 5-15R
(6) NEMA 5-15R (2) NEMA 5-20R T-slot
 Frequency
50 Hz or 60 Hz (± 0.5 Hz, auto-sensing)
 Waveform
Sine wave
 Overload Warning
> 100-110%
 Overload Shutdown
> 200% after 15 cycles
Battery Parameters
 Type
Valve-regulated, nonspillable, lead acid
 Battery Time (mins) (FL/HL)
11/26
5/16
5/16
 Qty. x Voltage  x Rating
4 x 12 V x 7 AH
4 x 12 V x 7 AH
6 x 12 V x 7 AH
 Transfer Time
2-6 ms typical
 Back-up Time
See Battery Run Time Charts
 Recharge Time
4 hours
to 95% capacity, after full discharge into 100% load
Environmental
 Operating  Temperature
+32°F to + 104°F (0°C to +40 C)
 Storage Temperature
+5°F to + 122°F (-15°C to +50°C)
 Relative Humidity
0% to 95%, non-condensing
 Operating Elevation
Up to 10,000 ft. (3000 m) at 35°C without derating
 Audible Noise
Max 50 dBA
Max 60 dBA
Agency
 Safety
UL 1778, c-UL Listed
 RFI/EMI
FCC Part 15, Class B
FCC Part 15, Class A
 Transportation ISTA Procedure 1A Certification
 Immunity
ANSI C62.41, EN61000-4-2, 3, 4, 5, 6, EN61000-3-2, 3

Note: These units are designed for EIA STD 19" wide rails and the UPS faceplate is 19" wide.

 

3K2U Extended Battery Options Top

Battery Cabinet Specifications

Catalog Number

S3K48BAT
S3K72BAT
 UPS Rated VA
1000
1440
2200
 Dimensions (H x W x D)
3.43" x 17" x 22"
(87 mm x 430 mm x 557 mm)
3.43" x 17" x 24"
(87 mm x 430 mm x 612 mm)
 Weight -  lbs (kg)
66.1 (30)
118.1 (53.6)
Battery Parameters
 Type
Valve-regulated, nonspillable, lead acid
 Qty. x Voltage  x Rating
2 strings of 4 x 12V x 7Ah
2 strings of 6 x 12V x 9Ah
 Back-up Time
See Battery Run Time Charts
 Recharge Time
4 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
 Operating  Temperature
+32°F to + 104°F (0°C to +40 C)
 Storage Temperature
+5°F to + 104°F (-15°C to +40°C)
 Relative Humidity
0% to 95%, non-condensing
 Operating Altitude
Up to 10,000 ft. (3000 m) at 35°C without derating
 Audible Noise
<40 dBA, internal fan(s) off, <55 dBA, internal fan(s) on
Agency
 Safety
UL 1778, cULus Listed, EN62040-1-1, TUV/GS Listed, CE Marked
 Emmisions
FCC Part 15, Class B; EN50091-2, Class B
 Transportation
ISTA Procedure 1A Certification


What's New | Products | Cross Reference
Technical Support | Contact Us | Search | Home

© 2004 Sola/Hevi-Duty. All Rights Reserved.