3K2U Rackmount 120 VAC |
 |
|
|
S3K2U1000
|
S3K2U1440
|
S3K2U2200
|
|
Power
Rating
(VA/Watts)
|
1000/750
|
1440/1080
|
2200/1650
|
|
Dimensions
inches (mm)
|
Unit
(H x W x D) |
3.43"
x 17" x 22"
(87 mm x 430 mm x 557 mm)
|
3.43"
x 17" x 24.1"
(87 mm x 430 mm x 612 mm) |
Shipping
(H x W x D) |
11.8"
x 23.5" x 27.8"
(300 mm x 598 mm x 706 mm)
|
13.1"
x 23.5" x 34"
(333 mm x 598 mm x 864 mm) |
Approx. Shipping
Weight - lbs (kg) |
81
(37)
|
86
(39)
|
96
(44)
|
|
Input
AC Parameters
|
| Voltage
Range |
78-150
VAC
|
| Surge
Protection |
570J
|
Voltage
Range Without
Battery |
78-150
VAC
|
| Frequency |
48-65
Hz ( ± 0.1 Hz)
|
| Input
Power Cord |
10
ft. (3m) attached NEMA5-15D
|
10ft.
(3m) attached NEMA L5-30P
|
|
Output
AC Parameters
|
| Voltage |
110/120/127
VAC ± 10% (configurable)
|
| Receptacles |
(8)
NEMA 5-15R
|
(8)
NEMA 5-15R
|
(6)
NEMA 5-15R (2) NEMA 5-20R T-slot
|
| Frequency |
50
Hz or 60 Hz (± 0.5 Hz, auto-sensing)
|
| Waveform |
Sine
wave
|
| Overload
Warning |
>
100-110%
|
| Overload
Shutdown |
>
200% after 15 cycles
|
|
Battery
Parameters
|
| Type |
Valve-regulated,
nonspillable, lead acid
|
| Battery
Time (mins) (FL/HL) |
11/26
|
5/16
|
5/16
|
| Qty.
x Voltage x Rating |
4
x 12 V x 7 AH
|
4
x 12 V x 7 AH
|
6
x 12 V x 7 AH
|
| Transfer
Time |
2-6
ms typical
|
| Back-up
Time |
See
Battery Run Time Charts
|
| Recharge
Time |
4
hours
|
|
to
95% capacity, after full discharge into 100% load
|
|
Environmental
|
|
Operating Temperature
|
+32°F
to + 104°F (0°C to +40 C)
|
| Storage Temperature |
+5°F
to + 122°F (-15°C to +50°C)
|
| Relative Humidity |
0%
to 95%, non-condensing
|
|
Operating Elevation
|
Up
to 10,000 ft. (3000 m) at 35°C without derating
|
| Audible
Noise |
Max
50 dBA
|
Max
60 dBA |
|
Agency
|
| Safety |
UL
1778, c-UL Listed
|
| RFI/EMI |
FCC
Part 15, Class B
|
FCC
Part 15, Class A |
| Transportation |
ISTA
Procedure 1A Certification |
| Immunity |
ANSI
C62.41, EN61000-4-2, 3, 4, 5, 6, EN61000-3-2, 3
|
Note:
These units are designed for EIA STD 19" wide rails and the
UPS faceplate is 19" wide.
|
3K2U Extended Battery Options |
 |
|
Battery
Cabinet Specifications
|
|
|
S3K48BAT
|
S3K72BAT
|
|
UPS
Rated VA
|
1000
|
1440
|
2200
|
|
Dimensions (H x W x D) |
3.43"
x 17" x 22"
(87 mm x 430 mm x 557 mm)
|
3.43"
x 17" x 24"
(87 mm x 430 mm x 612 mm) |
|
Weight - lbs (kg) |
66.1
(30)
|
118.1
(53.6)
|
|
Battery
Parameters
|
| Type |
Valve-regulated,
nonspillable, lead acid
|
| Qty.
x Voltage x Rating |
2
strings of 4 x 12V x 7Ah
|
2
strings of 6 x 12V x 9Ah
|
| Back-up
Time |
See
Battery Run Time Charts
|
| Recharge
Time |
4
hours to 90% of rated capacity, after full discharge into
resistive load
|
|
Environmental
|
|
Operating Temperature
|
+32°F
to + 104°F (0°C to +40 C)
|
| Storage Temperature |
+5°F
to + 104°F (-15°C to +40°C)
|
| Relative Humidity |
0%
to 95%, non-condensing
|
|
Operating Altitude
|
Up
to 10,000 ft. (3000 m) at 35°C without derating
|
| Audible
Noise |
<40
dBA, internal fan(s) off, <55 dBA, internal fan(s) on
|
|
Agency
|
| Safety |
UL
1778, cULus Listed, EN62040-1-1, TUV/GS Listed, CE Marked
|
| Emmisions |
FCC
Part 15, Class B; EN50091-2, Class B
|
| Transportation |
ISTA
Procedure 1A Certification
|