Sola/Hevi-Duty
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps/Distributors
Product Specials

PDF Links
Catalog Pages
Guide
Specifications


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.

Products
Home > Products > UPS > S3K Series > Specifications


S3K Specifications

A printable version of the following section is available by selecting the pdf file to the left.

120 VAC Top
 

 Catalog Number

S3K700
S3K1000
S3K1600
 Power Rating  
 
(VA/Watts)
700/480
1000/750
1440*/1200
Dimensions inches (mm)
 Unit (H x W x D)
8.3" x 5.5" x 17.2
(210 mm x 140 mm x 436 mm)
8.9" x 6.7" x 17.7"
(226 mm x 170 mm x 450 mm)
 Shipping 
 
(H x W x D)
11.75" x 10.5" x 19.2"
(300 mm x 265 mm x 492 mm)
14.0" x 12.0" x 22.25"
(358 mm x 307 mm x 581 mm)
 Approx. Shipping
 Weight -
lbs (kg)
34.1 (15.5)
37 (16.8)
70.4 (32)
Input AC Parameters
 Voltage Range
103-132 VAC
 Plug
6 ft. detachable with NEMA 5-15P
Attached 5-15P
 Voltage Raise
Maintains output to 120 VAC; -14%, when input is 120 VAC, -25%
 Voltage Lower
Maintains output to 120 VAC; +10%, when input is 120 VAC, +23%
 Frequency
45-55 Hz or 55-65 Hz; auto sensing
Output AC Parameters
 Voltage
103 VAC to 132 VAC
 Receptacles
(4) NEMA 5-15R
(6) NEMA 5-15R
 Frequency
50 Hz or 60 Hz ± 0.5%
 Waveform
Sine wave
 Overload Warning
100-110% Nominal
 Overload Shutdown
200% Nominal
Battery Parameters
 Type
Valve-regulated, nonspillable, lead acid
 Battery Time 
 
(mins) (FL/HL)
5/14
4/13
3/10
 Qty. x Voltage x  Rating
4 x 12 V x 7 AH
6 x 12 V x 7 AH
 Transfer Time
2-4 ms typical
 Back-up Time
See Battery Run Time Charts
 Recharge Time
4 Hours
to 90% capacity, after full discharge into 100% load
Environmental
 Operating  Temperature
+32°F to + 104°F (0°C to +40oC)
 Storage  Temperature
+5°F to + 122°F (-15°C to +50°C)
 Relative Humidity
0% to 95%, non-condensing
 Operating  Elevation
Up to 10,000 ft. (3000 m) at 35°C without derating
 Audible Noise
<40 dBA, (beyond 1 m)
<45 dBA, (beyond 1 m)
Agency
 Safety
UL 1778, cULus Listed
 RFI/EMI
FCC Part 15, Class B
 Immunity
IEC 801-2, Level 4 / IEC 801-4, Level 4 / IEEE 587 Category A

* Note: 1200W at 0.75 power factor equals 1600VA. Line cord limits total load to 1440 VA (max)


What's New | Products | Cross Reference
Technical Support | Contact Us | Search | Home

© 2004 Sola/Hevi-Duty. All Rights Reserved.