Catalog
Number
|
|
|
|
|
|
Capacity
(VA/Watts)
|
350/210
|
500/300
|
650/390 |
1000/6000
|
|
Dimensions-inches
(mm)
|
| Unit
(H x W x D) |
8.7" x 4.6" x 7.7"
(222 mm x 116 mm x 196 mm)
|
8.7"
x 4.6" x 14.1"
(222 mm x 116 mm x 358 mm)
|
| Shipping
(H x W x D) |
11.5"
x 7.7" x 12.2"
(293 mm x 196 mm x 310 mm)
|
12.4"
x 9.5" x 19.7"
(316 mm x 242 mm x 500 mm)
|
Approx.
Shipping
Weight-lbs(kg) |
18.1
(8.2)
|
18.5
(8.4)
|
22.9
(10.4) |
31.9
(14.5)
|
|
Input
AC Parameters
|
Voltage
Range w/out
Battery Operation |
78
to 150 VAC
|
Line
to Boost
Transfer |
104
VAC
|
| Line
to Buck Transfer |
124
VAC
|
| Frequency |
46.5
- 63.5 Hz (±0.1 Hz)
|
| Input
Power Cord |
6
ft. (1.8 m) detachable, with NEMA 5-15P
|
|
Output
AC Parameters
|
Voltage
(Battery Mode) |
120
VAC, ± 8%
|
| Receptacles |
(4)
NEMA 5-15R (orange) Battery backup + surge protection; (2)
NEMA 5-15R (black) Surge Protection
|
(6)
NEMA 5-15R (orange) Battery backup + surge protection; (2)
NEMA 5-15R (black) Surge Protection
|
Waveform
(Battery Mode) |
Stepped
Sinewave
|
| Voltage
(Normal) |
Nominal
(110, 120, 127 VAC) ± 10% configurable
|
|
Frequency
|
50
Hz or 60 Hz; auto sensing
|
Overload
Warning
(Utility and Battery Modes) |
>
100%
|
Overload
Shutdown
(Utility and Battery Modes) |
>
110%
|
|
Battery
Parameters
|
| Battery
Type |
Valve-Regulated
Lead Acid, Non-spillable
|
Battery
Qty x
Voltage x Rating |
(1)
x 12 V x 7 AH
|
(1)
x 12 V x 9AH
|
(2)
x 12 V x 7.5 AH
|
| Transfer
Time |
4-6
ms typical
|
| Back-up
Time: |
|
|
Full Load
|
8
minutes
|
8
minutes
|
5
minutes
|
5
minutes
|
|
Half Load
|
26
minutes
|
24
minutes
|
16
minutes
|
18
minutes
|
| Recharge
Time |
6
hours to 90% capacity, after full discharge into 100% resistive
load
|
|
Environmental
|
Operating
Temperature |
+32oF
to +104oF
(0oC
to +40oC)
|
| Storage
Temperature |
+5oF
to +104oF
(-15oC
to +40oC)
|
| Relative
Humidity |
0%
to 90%, non-condensing
|
| Operating
Elevation |
Up
to 10,000 ft. (3000 m) at 86oF
(30oC)
without derating
|
| Audible
Noise |
Less
than 40 dB @ 1 meter
|
|
Agency
|
| Safety |
UL
1778, C-UL Listed
|
| ESD |
EN61000-4-2,
Level 3, Criteria A
|
| Surge
Protection |
ANSI
C62.41, Category A, Level 3 (IEEE 587, Category A); EN61000-4-5,
Level 3, Criteria A
|
| Susceptibility
|
EN61000-4-3,
Level 3, Criteria A
|
Electrical
Fast
Transient/Burst |
EN61000-4-4,
Level 4, Criteria A
|
| Emissions |
FCC
Part 15, Subpart B, Class B
|